How many fire extinguishers do I need, and which types?

The BS 5306-8 rules of thumb for coverage, the class-by-class guide to types, and the three mistakes that appear on almost every fire risk assessment.

Equipment · 4 min read · Updated 21 October 2026 · Next review September 2027

BS 5306-8 gives a method for working out extinguisher provision, and the fire risk assessment refines it for the building. The basics are straightforward.

Class A coverage

For ordinary combustibles (paper, wood, textiles) the standard requires a minimum of two Class A extinguishers on every floor with a combined rating of at least 26A, unless the floor is very small. The total A rating should be at least 0.065 multiplied by the floor area in square metres. Nobody should have to travel more than 30 metres to reach one. A typical 9-litre water or 6-litre foam extinguisher is rated 13A, so two per floor is the usual minimum.

Special risks

RiskExtinguisher
Electrical equipment, server rooms, switchroomsCO2 (2 kg or 5 kg)
Commercial kitchens with deep fat fryersWet chemical (Class F) plus fire blanket
Flammable liquids, workshops, plant roomsFoam (fluorine-free) or dry powder
Vehicles, outdoor plant, gasDry powder
E-bike and scooter stores, battery roomsLithium-ion battery extinguisher and specialist advice

The three common mistakes

  • Dry powder indoors. It is effective but the cloud blinds and chokes in enclosed spaces; BS 5306-8 discourages it inside except where nothing else will do.
  • Extinguishers mounted where nobody can see them, or on the floor behind a door. They belong on exit routes, at conspicuous positions, at a consistent height, with a location sign.
  • Missing the annual service. An out-of-date extinguisher is a finding on every fire risk assessment and, after use, may not work.