Dry risers: what the annual test involves and why blocks fail it

A dry riser gets a firefighter’s water to the upper floors. BS 9990 requires a wet pressure test every year and a visual inspection every six months. Here is what happens and what usually goes wrong.

Equipment · 4 min read · Updated 21 October 2026 · Next review September 2027

In buildings taller than about 18 metres, or where the fire appliance cannot get close, a dry rising main gives firefighters a pipe already in the building. They connect at the inlet at ground level, pump water up the main and connect hose at the landing valve on the fire floor. It only works if every part is intact.

Six-monthly visual inspection

Every inlet and landing valve cabinet is opened and checked: the door and glazing, padlock and strap, the cap and chain on each outlet, the valve handwheel and spindle, the blank caps, the drain valve, the signage and the pipework where visible. Vandalism, theft of brass fittings and missing caps are the commonest findings.

Annual wet test

The main is filled from a test pump and pressurised to 12 bar for 15 minutes. Every landing valve is checked for leaks and free operation, the inlet breeching non-return valves are checked, and the pressure is monitored for any drop. After the test the main is drained fully and the drain valve closed and secured. A certificate is issued with the result for each outlet.

Under the 2022 Regulations the responsible person for a residential building over 11 metres must check firefighting equipment monthly and, over 18 metres, tell the Fire and Rescue Service where the risers are and report faults. Our inspection reports are written to support both duties.

Why blocks fail

  • Missing or damaged outlet caps, so the main cannot be pressurised.
  • Seized landing valves that have not been exercised.
  • Leaking joints from corrosion or impact damage.
  • Inlet cabinets blocked by bins, parking or landscaping so an appliance cannot reach them.