Fixed fire suppression systems

Gaseous, watermist and kitchen suppression systems for server rooms, switchrooms, archives, plant and commercial kitchens, designed to BS EN 15004, BS 8489 and LPS 1223 and maintained annually.

Some rooms cannot wait for the fire brigade. A server room, a switchroom, an archive or a kitchen line needs a system that detects and extinguishes automatically, in seconds, without wrecking what it protects. We design, install and maintain fixed suppression systems matched to the risk and the asset.

Systems

  • Inert gas (IG-541, IG-55, IG-100) and clean agent (FK-5-1-12) systems for IT, electrical and archive rooms.
  • Watermist to BS 8489 for plant rooms, generators, heritage buildings and residential applications.
  • Kitchen suppression to LPS 1223 for cooking lines, canopies and ducts.
  • In-cabinet and micro-environment systems for individual racks and enclosures.
  • Detection and control: coincidence detection, aspirating detection and extract shutdown integrated with the fire alarm.

Maintenance

Six-monthly inspections check cylinder pressure and weight, actuators, detection, warning signs and the control panel. Annual servicing adds a full functional test and a room integrity test. Cylinders are pressure-tested to the schedule and we manage the paperwork for the transportable pressure equipment regulations.

Frequently asked

Which agent should I use in a server room?

Inert gases (IG-541, IG-55, nitrogen) and clean chemical agents (FK-5-1-12) both protect electronics without residue. Inert gas needs more cylinder storage; clean agents need less space but cost more per kilo. We size both and let you compare over a 15-year life including the room integrity requirements.

Why does the room need integrity testing?

A gas system only works if the room holds the concentration for long enough, usually ten minutes. A door fan integrity test to BS EN 15004 Annex E measures the leakage and predicts the hold time. It is required at commissioning and annually.

What about kitchen canopies?

Wet chemical kitchen suppression to LPS 1223 or UL 300 protects the cooking line, canopy and duct, and interlocks with the gas supply. Insurers increasingly require it for commercial kitchens.