Gas leaks do not announce themselves. Fixed gas detection provides continuous monitoring of the spaces where a leak would be most dangerous, and can act automatically to shut off supply and clear the atmosphere before anyone is hurt.
Applications
- Boiler houses and plant rooms: methane, LPG and carbon monoxide.
- Commercial kitchens: gas interlock with proving, detection and ventilation control.
- Enclosed and basement car parks: carbon monoxide and NO2 linked to ventilation.
- Refrigeration plant rooms and cold stores: refrigerant leak detection to BS EN 378.
- Laboratories and battery rooms: hydrogen, oxygen depletion and toxic gases.
Design and maintenance
Sensor placement is everything: heavy gases pool at floor level, light gases collect at the ceiling, and air movement changes both. We survey the space, position sensors accordingly, and interlock the system to gas valves, ventilation and the fire alarm or BMS as the risk assessment requires. Sensors are calibrated with certified test gas on a six-monthly cycle and every reading is recorded.
Frequently asked
Which spaces need gas detection?
Commonly boiler rooms and plant rooms with gas appliances, commercial kitchens with a gas interlock, enclosed car parks (CO), refrigeration plant rooms (refrigerant), laboratories and any space where DSEAR identifies an explosive atmosphere risk.
How often do sensors need calibrating?
Most manufacturers specify six-monthly calibration with test gas and a maximum sensor life of two to five years depending on the gas. We calibrate on planned visits and record the sensor serial number, reading and next-due date.
Can the system shut the gas off?
Yes. A gas-proving and detection system can close the solenoid valve on the incoming gas supply and start extract ventilation, which is standard in commercial kitchens under IGEM/UP/19 and BS 6173.